이중 변환 UPS의 병렬 운전 시 외란 저감 성능 향상을 위한 정지 좌표계 상의 전향 보상 기법
- Title
- 이중 변환 UPS의 병렬 운전 시 외란 저감 성능 향상을 위한 정지 좌표계 상의 전향 보상 기법
- Other Titles
- Feed-Forward Compensation Technique in Stationary Reference Frame for the Enhanced Disturbance Rejection Performance in Parallel Operation of Double-Conversion UPSs
- Author
- 윤영두
- Keywords
- UPS(Uninterruptible Power Supply); Proportional-resonant controller; Feed-forward control; Circulating current impedance; 2-DOF(Two-Degree of Freedom) control
- Issue Date
- 2022-10
- Publisher
- 전력전자학회
- Citation
- 전력전자학회 논문지, v. 27, NO. 5, Page. 367-375
- Abstract
- Generally, a proportional-resonant controller is used to eliminate steady-state errors during the voltage-current control of a double-conversion uninterruptible power supply (UPS) in a stationary reference frame. Additionally, the feed-forward control compensating for the load current, which can be considered a disturbance of the voltage controller, can be used to improve the disturbance rejection performance. However, during the parallel operation of UPSs, circulating current can occur between UPS modules when performing both feed-forward control and droop control because feed-forward control reduces the circulating current impedance. This study proposes a feed-forward compensation technique that considers the impedance of circulating current. An additional feed-forward compensation technique is developed to enhance the disturbance rejection performance. The validity of the proposed feed-forward compensation technique is verified by the experiment results of the parallel operation of a 500 W double-conversion UPS module.
- URI
- http://koreascience.or.kr/article/JAKO202229753996589.pagehttps://repository.hanyang.ac.kr/handle/20.500.11754/177952
- ISSN
- 1229-2214;2288-6281
- DOI
- 10.6113/TKPE.2022.27.5.367
- Appears in Collections:
- COLLEGE OF ENGINEERING[S](공과대학) > AUTOMOTIVE ENGINEERING(미래자동차공학과) > Articles
- Files in This Item:
There are no files associated with this item.
- Export
- RIS (EndNote)
- XLS (Excel)
- XML