식물공장을 위한 연료전지가 적용된 제습공조시스템의 에너지 절감효과 분석
- Title
- 식물공장을 위한 연료전지가 적용된 제습공조시스템의 에너지 절감효과 분석
- Other Titles
- Energy Saving Potential of Desiccant-Assisted Air Conditioning System Integrated with PEMFC for Smart Farm
- Author
- 정재원
- Keywords
- Liquid desiccant; Plant factory; PEMFC; Carbon dioxide; 액체식 제습제; 식물공장; 이산화탄소
- Issue Date
- 2020-11
- Publisher
- (사)대한설비공학회
- Citation
- 대한설비공학회 동계학술발표회 논문집, page. 55-58
- Abstract
- This paper aimed to analyze the annual energy consumption of the heat pump-driven liquid desiccant (HPLD) system combined with a fuel cell in the plant factory. Through simulation, it is found that in a plant factory with an area of 200 square meters, the HPLD air conditioning system only needs 48.12MWh of fuel and 25.66MWh of electricity for operation throughout the year. The proton exchange membrane fuel cell (PEMFC) selected in this study can meet 79.9% of the electricity and 76.4% of the heat demand of this plant factory. At the same time, fuel cell by-products (i.e., water and carbon dioxide) can be supplied to plants. It can meet 7.2% of the daily water demand of plants and reduce 18.5% of carbon dioxide emissions.
- URI
- https://www.auric.or.kr/User/Rdoc/DocRdoc.aspx?BrsDataBaseName=RDOC&PrimaryKey=402578&DBNM=RDCR#.YwbQuHZByUkhttps://repository.hanyang.ac.kr/handle/20.500.11754/172704