167 0

Chaotic analysis of Partial Discharge(CAPD)

Title
Chaotic analysis of Partial Discharge(CAPD)
Other Titles
A Novel Approach to Identify the Nature of PD Source based on the Chaotic Time Series Analysis Technique
Author
구자윤
Keywords
PRPDA; CAPD; on-line monitoring; partial discharge; large power apparatus
Issue Date
2002-02
Publisher
대한전기학회
Citation
KIEE International Transactions on Electrophysics and Applications, v. 12C, no. 1, page. 15-23
Abstract
In connection with the monitoring of insulation degradation of large power apparatus in order to predict thier expected service failures, a statistical treatment, such as phase resolved partial discharge analysis(PRPDA), has been established for the on-line monitoring system during the past decades. However, this method has shown some inconveniences to identify the nature of PD source in power apparatus. Moreover, because all discharge pulses are superimposed within a certain number of phase windows, no correlation between pulses in the same or different cycles of the applied voltage is taken into account. In this regard, a novel approach based on the chaotic time series analysis technic(CAPD) is proposed.
URI
http://www.dbpia.co.kr/journal/articleDetail?nodeId=NODE01314145https://repository.hanyang.ac.kr/handle/20.500.11754/156821
ISSN
1598-2610
Appears in Collections:
COLLEGE OF ENGINEERING SCIENCES[E](공학대학) > ELECTRICAL ENGINEERING(전자공학부) > Articles