Abstract
This paper describes the improvement of the arithmetic for emergency generator capacity. This formula which calculates emergency generator is dependent on the Korean Design Standard of building electrical equipment issued by the Ministry of Land, Infrastructure and Transport, and the technical data related to the generator. when appling the formula, the capacity of the generator is insufficient at the starting conditions of the load facility. In case of emergency, the generator is not operated normally. of the formula (, , ) applied in determining the capacity of the emergency generator is selected by calculating the capacity of the generator based on only biggest one motor among the load equipment and may not be able to start the generator normally in case of emergency because there is an error such that the power factor is applied at the last start of the motor having the maximum capacity of the load. We analyze the problem of capacity calculation of emergency generators used for general purposes. As a consequence, the improved formulas have been presented for safety of electrical installation.
URI
http://koreascience.or.kr/article/JAKO201835372350513.pagehttps://repository.hanyang.ac.kr/handle/20.500.11754/120683
ISSN
1975-8359; 2287-4364
DOI
10.5370/KIEE.2018.67.11.1517
Appears in Collections:
COLLEGE OF ENGINEERING[S](공과대학) > ELECTRICAL AND BIOMEDICAL ENGINEERING(전기·생체공학부) > Articles
Files in This Item:
비상발전기용량 산정식 개선에 관한 연구.pdfDownload
Export
RIS (EndNote)
XLS (Excel)
XML


qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

BROWSE