231 421

Impact of Heat Pump-Driven Liquid Desiccant Dehumidification on the Energy Performance of an Evaporative Cooling-Assisted Air Conditioning System

Title
Impact of Heat Pump-Driven Liquid Desiccant Dehumidification on the Energy Performance of an Evaporative Cooling-Assisted Air Conditioning System
Author
정재원
Keywords
liquid desiccant system; evaporative cooling system; 100% outdoor air system; heat pump-driven liquid desiccant system; heat recovery
Issue Date
2018-02
Publisher
MDPI
Citation
ENERGIES, v. 11, no. 2, Article no. 345
Abstract
The main objective of this research is to investigate the energy performance enhancement obtained by applying a heat pump to a liquid desiccant and indirect and direct evaporative cooling-assisted 100% outdoor air system (LD-IDECOAS). In conventional LD-IDECOAS operation, the boiler providing regeneration heat to the weak desiccant solution consumes most of the energy. In order to reduce the regeneration energy consumption in the LD-IDECOAS, a heat pump-integrated LD-IDECOAS (HPLD-IDECOAS) is suggested in this research. The heat pump reclaims waste heat from the absorber side of the system, and delivers the reclaimed heat to the regenerator side. Detailed energy simulations for both the LD-IDECOAS and HPLD-IDECOAS were conducted to analyze the energy saving potentiality of the proposed system over the conventional LD-IDECOAS. In both systems, it was assumed that a packed-bed type liquid desiccant unit with an aqueous solution of lithium chloride (LiCl) was used. In the proposed system, a heat pump with R-134a refrigerant was adopted. The results show that the proposed system was able to provide a 33% reduction in annual primary energy consumption compared with the conventional LD-IDECOAS. This significantly enhanced energy performance was mainly obtained through an 83% reduction in the gas energy consumed for regeneration of the desiccant solution in the proposed system by applying the heat pump.
URI
https://www.mdpi.com/1996-1073/11/2/345https://repository.hanyang.ac.kr/handle/20.500.11754/117569
ISSN
1996-1073
DOI
10.3390/en11020345
Appears in Collections:
COLLEGE OF ENGINEERING[S](공과대학) > ARCHITECTURAL ENGINEERING(건축공학부) > Articles
Files in This Item:
Impact of Heat Pump-Driven Liquid Desiccant Dehumidification on the Energy Performance of an Evaporative Cooling-Assisted Air Conditioning System.pdfDownload