188 0

Thermal and drainage performance of a louvered fin heat exchanger according to heat exchanger inclination angle under frosting and defrosting conditions

Title
Thermal and drainage performance of a louvered fin heat exchanger according to heat exchanger inclination angle under frosting and defrosting conditions
Author
이관수
Keywords
Frosting; Heat exchanger; Inclination angle; Drainage
Issue Date
2017-05
Publisher
PERGAMON-ELSEVIER SCIENCE LTD
Citation
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, v. 108, page. 1335-1339, Part:B
Abstract
We carried out experiments of repeated frosting/defrosting cycles while varying the heat exchanger inclination angles (0 degrees, 15 degrees, 30 degrees, and 45 degrees) of a louvered fin heat exchanger and analyzed the variations in thermal performance, residual water, and defrosting efficiency according to the heat exchanger inclination angle. For larger inclination angles, the heat transfer rate and pressure drop varied less during repeated cycling. The use of high inclination angles improved the drainage performance of the louvered fin heat exchanger and reduced the mass of its residual water. The defrosting efficiency varied less during repeated cycling for high inclination angles than for low inclination angles. (C) 2017 Elsevier Ltd. All rights reserved.
URI
https://www.sciencedirect.com/science/article/pii/S0017931016335967?via%3Dihubhttps://repository.hanyang.ac.kr/handle/20.500.11754/114116
ISSN
0017-9310; 1879-2189
DOI
10.1016/j.ijheatmasstransfer.2017.01.043
Appears in Collections:
COLLEGE OF ENGINEERING[S](공과대학) > MECHANICAL ENGINEERING(기계공학부) > Articles
Files in This Item:
There are no files associated with this item.
Export
RIS (EndNote)
XLS (Excel)
XML


qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

BROWSE