284 0

계통연계형 태양광 발전 시스템의 부하 모효전력 보상이 적용된 단독운전 인지법

Title
계통연계형 태양광 발전 시스템의 부하 모효전력 보상이 적용된 단독운전 인지법
Other Titles
The Anti-Islanding Method with Compensation of Load Reactive Power for Grid-connected Photovoltaic Generation System
Author
김희준
Keywords
Photovoltaic generation system; Anti-islanding; Reactive power control; Reactive power compensation
Issue Date
2008-01
Publisher
대한전기학회
Citation
전기학회논문지, v. 57, No. 1, Page. 58-64
Abstract
In this paper, we present an active anti-islanding method with a load monitoring system using reactive power control. The proposed method, which is based on reactive power control, has fewer harmonics components than those in conventional methods, and it can minimize the reactive power component of the grid because it compensates the reactive power component with the load monitoring. The proposed quick islanding detection method was confirmed from the experimental results with an inverter for a 3㎾ photovoltaic system.
URI
http://www.dbpia.co.kr/Journal/ArticleDetail/NODE01278632https://repository.hanyang.ac.kr/handle/20.500.11754/104275
ISSN
1975-8359
Appears in Collections:
COLLEGE OF ENGINEERING SCIENCES[E](공학대학) > ELECTRICAL ENGINEERING(전자공학부) > Articles