변풍량 공조시스템의 외기냉방 운전 시 대기질 지수 고려에 의한 실내 PM2.5 농도 개선효과 분석

Title
변풍량 공조시스템의 외기냉방 운전 시 대기질 지수 고려에 의한 실내 PM2.5 농도 개선효과 분석
Other Titles
Analysis of Indoor PM2.5 Concentration Improvement Effect by Considering Air Quality Index under Air-side Economizer of VAV system
Author
정재원
Keywords
외기냉방 운전; 실내 공기질; 초미세먼지; 대기질 지수; Air-side economizer; Indoor Air Quality (IAQ); PM2.5; Air Quality Index (AQI)
Issue Date
2016-04
Publisher
대한건축학회
Citation
대한건축학회, v. 36, NO 1, Page. 261-262
Abstract
Recently, the active researches have been made in Air-side economizer for saving HVAC energy. In spite of this advantage, however, outdoor air quality is getting worse due to industrialization. It has a direct impact on occupants’ health in building when Air-side economizer operates. Therefore, this study suggested an operation of Air-side economizer method which differs depending on outdoor air quality. The effects of indoor air quality improvement was verified by the simulation study using Open studio, Energy Plus and Excel programs. This study used Air Quality Index defined by U.S. Environmental Protection Agency as an indicator for judging outdoor air quality. As a result, in view of Korea PM2.5 standard (average 24 PM2.5 50㎍/㎥), PM2.5 standard overtime deceased from 432 hours to 373 hours (reduced 13.49%) and annual average PM2.5 concentration decreased from 20.4 ㎍/㎥ to 19.7 ㎍/㎥ (reduced 3.43%) when variable air volume (VAV) system with MERV 9 was applied. By contrast, there was 0.78% increase in annual Chiller, Pumps and Fan energy consumption
URI
http://www.dbpia.co.kr/Journal/ArticleDetail/NODE06651119http://hdl.handle.net/20.500.11754/43619
ISSN
2287-5786
Appears in Collections:
COLLEGE OF ENGINEERING[S](공과대학) > ARCHITECTURAL ENGINEERING(건축공학부) > Articles
Files in This Item:
There are no files associated with this item.
Export
RIS (EndNote)
XLS (Excel)
XML


qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

BROWSE