Local frosting behavior of a plated-fin and tube heat exchanger according to the refrigerant flow direction and surface treatment

Title
Local frosting behavior of a plated-fin and tube heat exchanger according to the refrigerant flow direction and surface treatment
Author
김동립
Keywords
Frost formation; Refrigerant flow inlet direction; Surface treatment; Defrosting
Issue Date
2013-06
Publisher
PERGAMON-ELSEVIER SCIENCE LTD
Citation
International journal of heat and mass transfer, 2013, 64, p.751 - 758
Abstract
Heat pumps have been promoted as energy-efficient heating and cooling systems. However, in the heating mode, heat pump performance is often significantly degraded by the frost layer that forms on the fin surface of the heat exchanger due to the low temperature of the outdoor unit. In this research, we experimentally investigated the thermal performance and frosting behavior at various locations on a plate-fin and tube heat exchanger with respect to refrigerant flow direction (counter-flow and parallel-flow) and fin surface treatment (bare, hydrophilic, hydrophobic, and hybrid). On the bare heat exchanger, the frost growth was more uniform with a counter-flow than with a parallel-flow, and thus the overall heat transfer rate was higher under counter-flow condition. The performance difference between the counter-flow and parallel-flow conditions became more significant when the heat exchanger was operated at lower refrigerant temperature and air velocity. Although the initial heat transfer rate of the hydrophilic unit was the highest among the surface-treated heat exchangers, this unit also suffered a dramatic reduction in the heat transfer rate because of the fast frost growth and non-uniform frosting behavior on its rear side. On the other hand, although the hydrophobic heat exchanger had a slightly lower initial heat transfer rate than the hydrophilic unit, it exhibited a consistent heat transfer rate throughout the experiment, owing to the frost retardation effect and the relatively uniform frosting behavior on its rear side. Each of the hybrid hydrophilic-hydrophobic surface-treated heat exchangers showed a lesser reduction of the heat transfer rate than the hydrophilic unit, and a higher initial heat transfer rate than the hydrophobic unit. (C) 2013 Elsevier Ltd. All rights reserved.
URI
https://www.sciencedirect.com/science/article/pii/S0017931013004171http://hdl.handle.net/20.500.11754/46424
ISSN
0017-9310
DOI
10.1016/j.ijheatmasstransfer.2013.05.027
Appears in Collections:
COLLEGE OF ENGINEERING[S](공과대학) > MECHANICAL ENGINEERING(기계공학부) > Articles
Files in This Item:
There are no files associated with this item.
Export
RIS (EndNote)
XLS (Excel)
XML


qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

BROWSE