dc.description.abstractThis paper presents a nonlinear feedback controller for a permanent-magnet synchronous generator (PMSG) wind turbine system based on port-controlled Hamiltonian system. For the simplification, this work focuses on the nonlinear control law of the grid side converter (GSC) that is directly connected to the grid and affected during network disturbances. The proposed controller is designed through the analysis of PMSG GSC model from the passivity viewpoint in order to regulate the reference of the DC voltage and track the reference of the reactive current. The exponential stability of the equilibrium point of the error dynamics at the origin is guaranteed by using Lyapunov theory. Finally, the proposed method is validated through simulation. The simulation results show that the performance has smaller overshoot and faster convergence when the proposed method is used than when the conventional method is used.en_US
dc.description.sponsorshipThis research was supported by Korea Electric Power Corporation Research Institute through Korea Electrical Engineering & Science Research Institute [grant number : R13EA03].en_US
dc.language.isoenen_US
dc.publisherINST CONTROL ROBOTICS & SYSTEMSen_US
dc.subjectExponential stabilityen_US
dc.subjectpassivityen_US
dc.subjectport-controlled Hamiltonian systemen_US
dc.subjectPMSG wind turbineen_US
dc.titleImproved Low-voltage Ride through Capability for PMSG Wind Turbine Based on Port-controlled Hamiltonian Systemen_US
dc.typeArticleen_US
dc.relation.no5-
dc.relation.volume14-
dc.identifier.doi10.1007/s12555-014-0480-y-
dc.relation.page1195-1204-
dc.relation.journalINTERNATIONAL JOURNAL OF CONTROL AUTOMATION AND SYSTEMS-
dc.contributor.googleauthorGui, Yonghao-
dc.contributor.googleauthorKim, Chunghun-
dc.contributor.googleauthorChung, Chung Choo-
dc.relation.code2016010333-
dc.sector.campusS-
dc.sector.daehakCOLLEGE OF ENGINEERING[S]-
dc.sector.departmentDIVISION OF ELECTRICAL AND BIOMEDICAL ENGINEERING-
dc.identifier.pidcchung-
Appears in Collections:
COLLEGE OF ENGINEERING[S](공과대학) > ELECTRICAL AND BIOMEDICAL ENGINEERING(전기·생체공학부) > Articles
Files in This Item:
There are no files associated with this item.
Export
RIS (EndNote)
XLS (Excel)
XML


qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

BROWSE