Abstract
This research is a case study performing the air-handler fan pressurization test in two office building. The test has been following the existing test standard(i.e. ASTM E779-10, CAN/CGSB-149.15-96 Standard). The test building is a 5-story office with a square(32.4m x 32.4m) footprint built in 2001 at Daejeon. Another test building is a 12-story offce building with a square(34.9m x 34.9m) at Seoul. Before the test, the standards about air leakage test is analyzed. Then, the pressure difference measurement is apply to ASTM standard. To measure the whole building envelope leakage, the air-handler units operated at the 100% outdoor air mode with closed RA dampers, EA dampers. This results is represent to ACH50, ELA, EqLA compared to other standards. This paper provides some practical information acquired in the field measurement of air tightness test using the established air-handler fan pressurization test method.
URI
https://www.kci.go.kr/kciportal/ci/sereArticleSearch/ciSereArtiView.kci?sereArticleSearchBean.artiId=ART001783243http://hdl.handle.net/20.500.11754/45642
ISSN
1226-9093
Appears in Collections:
COLLEGE OF ENGINEERING[S](공과대학) > ARCHITECTURAL ENGINEERING(건축공학부) > Articles
Files in This Item:
There are no files associated with this item.
Export
RIS (EndNote)
XLS (Excel)
XML


qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

BROWSE