318 0

Development of a partial discharge detection algorithm and verification test for extra-high-voltage cable system

Title
Development of a partial discharge detection algorithm and verification test for extra-high-voltage cable system
Author
구자윤
Keywords
LOCATION; PULSES; PD
Issue Date
2016-03
Publisher
INST ENGINEERING TECHNOLOGY-IET
Citation
IET SCIENCE MEASUREMENT & TECHNOLOGY, V. 10, No. 2, Page. 111-119
Abstract
Even though a lot of research has been devoted to find partial discharge (PD) sources based on the time difference of pulses, it has been reported that studies have been unable to obtain precise locations in joints due to the errors caused by the attenuation or distortion of PD pulses. In this study, in order to reduce the issues, ‘Precise PD finding’ is developed to obtain the accurate locations of PD sources by considering not only the time difference of pulses, but also pulse polarity. Accordingly, a PD detection algorithm is implemented. An attachable inductive sensor is designed and fabricated and then applied to a real scaled 154 kV XLPE cable with a joint. From the experimental results, the algorithm was verified to successfully find the locations of PD sources. The algorithm was then applied to an on-site, 345 kV XLPE cable. Consequently, PD sources were detected in a normal straight joint box and confirmed through a disassembly investigation.
URI
http://digital-library.theiet.org/content/journals/10.1049/iet-smt.2015.0125http://hdl.handle.net/20.500.11754/40932
ISSN
1751-8822; 1751-8830
DOI
10.1049/iet-smt.2015.0125
Appears in Collections:
COLLEGE OF ENGINEERING SCIENCES[E](공학대학) > ELECTRICAL ENGINEERING(전자공학부) > Articles