Abstract
This paper examines the insulation performance of synthetic air and dry air. This examination was conducted based on dielectric strength in uniform and non-uniform field, electric field distribution by interior structure and defects in gas insulation switchgear (GIS) and insulation performance in different temperatures. From this review, it was found that eco-insulation gas required to possess low moisture content for power equipment in the distribution class. The results of this paper are valuable to ensure the insulation design and insulation reliability of GIS using air.