dc.identifier.citationAPPLIED THERMAL ENGINEERING, v. 182, article no. 116094en_US
dc.identifier.issn1359-4311en_US
dc.identifier.urihttps://www.sciencedirect.com/science/article/pii/S1359431120335742?via%3Dihuben_US
dc.identifier.urihttps://repository.hanyang.ac.kr/handle/20.500.11754/177065-
dc.description.abstractThe energy and operating performances of a vacuum membrane dehumidification system were theoretically investigated for building air conditioning applications. The dehumidification effectiveness and coefficient of performance (COP) were adopted as performance indices. A one-dimensional mass-transfer model was derived to analyze the effect of each operating parameter on dehumidification performance. The data predicted by the model agreed well with measured results, with an error bound of 20%. Parametric analysis results indicated that the vacuum side pressure had the most significant impact on the energy and dehumidification performances. It was also observed that the membrane module length plays an important role in the module design. Based on the analysis results, a configuration and operating strategy of a vacuum membrane dehumidifier-assisted variable air volume air conditioning system were suggested. Subsequently, the proposed system was evaluated by comparing its energy and operating performances with those of the conventional variable air volume air system via energy simulations. The results indicated that the total primary energy consumption from the proposed system was 8.2% lower than that of the conventional system. However, the fan energy consumption in the proposed system was 2.5 times higher than that of the conventional system owing to the high pressure drop of membrane module. In addition, the proposed system consumed 7.7% more primary energy for dehumidification and sensible cooling process because of its lower COP. To achieve comparable energy performance, further research on the optimized design of a membrane module and optimized operation of a vacuum pump in the proposed system are necessary.en_US
dc.description.sponsorshipThis work was supported by the National Research Foundation of Korea (NRF) grant (No. 2019R1A2C2002514) and the Korean Institute of Energy Technology Evaluation and Planning (KETEP) (No. 20184010201710).en_US
dc.languageenen_US
dc.publisherPERGAMON-ELSEVIER SCIENCE LTDen_US
dc.subjectVacuum-based membrane dehumidificationen_US
dc.subjectIsothermal dehumidificationen_US
dc.subjectNumerical analysisen_US
dc.subjectEnergy simulationen_US
dc.subjectHVAC applicationen_US
dc.titleEnergy impact of vacuum-based membrane dehumidification in building air-conditioning applicationsen_US
dc.typeArticleen_US
dc.relation.volume182-
dc.identifier.doi10.1016/j.applthermaleng.2020.116094en_US
dc.relation.journalAPPLIED THERMAL ENGINEERING-
dc.contributor.googleauthorCho, Hye-Jin-
dc.contributor.googleauthorCheon, Seong-Yong-
dc.contributor.googleauthorJeong, Jae-Weon-
dc.sector.campusS-
dc.sector.daehak공과대학-
dc.sector.department건축공학부-
dc.identifier.pidjjwarc-
Appears in Collections:
COLLEGE OF ENGINEERING[S](공과대학) > ARCHITECTURAL ENGINEERING(건축공학부) > Articles
Files in This Item:
There are no files associated with this item.
Export
RIS (EndNote)
XLS (Excel)
XML


qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

BROWSE