Energy saving potential of a model-predicted frost prevention method for energy recovery ventilators

Title
Energy saving potential of a model-predicted frost prevention method for energy recovery ventilators
Author
정재원
Keywords
Model-predicted control; Energy recovery ventilator; Frost prevention; Condensation; Temperature control
Issue Date
2021-02
Publisher
PERGAMON-ELSEVIER SCIENCE LTD
Citation
APPLIED THERMAL ENGINEERING, v. 185, article no. 116450
Abstract
This study evaluates the energy-saving potential of a prediction model-based pre-heat coil operation method for frost prevention in energy recovery ventilators, compared to existing approaches. Energy recovery ventilator (ERV) requires pre-heating of the incoming outdoor air to prevent undesirable condensation and frost formation in the enthalpy exchanger during winter. Conventionally, the introduced outdoor air is pre-heated to a certain constant temperature using a pre-heat coil, resulting in unnecessary energy consumption. Maintaining a constant pre-heat temperature during the operation of the ERV is not ideal as the frost threshold temperature varies with the outdoor air temperature and humidity. Therefore, to reduce pre-heating energy consumption, a prediction model-based pre-heat coil operation method is proposed herein. A numerical model predicting the frost threshold temperature based on the outdoor air and exhaust air conditions was developed, and validated using the optimal Latin hypercube design method. Subsequently, a series of energy simulations was performed considering an identical residential model, located in 8 cities with different climatic conditions, to evaluate the energy-saving potential of the proposed pre-heat coil operation method compared to conventional methods. The proposed method consumed 7%-72% less energy in the ERV operation and required a 1%-21% smaller pre-heat coil capacity than the conventional method. Thus, the proposed operation method is superior to the conventional method as it prevents frost formation and consumes a minimal amount of energy.
URI
https://www.sciencedirect.com/science/article/pii/S1359431120339260?via%3Dihubhttps://repository.hanyang.ac.kr/handle/20.500.11754/177062
ISSN
1359-4311
DOI
10.1016/j.applthermaleng.2020.116450
Appears in Collections:
COLLEGE OF ENGINEERING[S](공과대학) > ARCHITECTURAL ENGINEERING(건축공학부) > Articles
Files in This Item:
There are no files associated with this item.
Export
RIS (EndNote)
XLS (Excel)
XML


qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

BROWSE