283 122

Full metadata record

DC FieldValueLanguage
dc.contributor.author정재원-
dc.date.accessioned2021-03-04T00:36:48Z-
dc.date.available2021-03-04T00:36:48Z-
dc.date.issued2020-02-
dc.identifier.citationENERGIES, v. 13, no. 3, article no. 522en_US
dc.identifier.issn1996-1073-
dc.identifier.urihttps://www.mdpi.com/1996-1073/13/3/522-
dc.identifier.urihttps://repository.hanyang.ac.kr/handle/20.500.11754/160246-
dc.description.abstractThis study investigated the annual energy saving potential and system performance of two different evaporative cooling-based liquid desiccant and evaporative cooling-assisted air conditioning systems. One system used an indirect and direct evaporative cooler with a two-stage package to match the target supply air point. The other was equipped with a single-stage, packaged dew-point evaporative cooler that used a portion of the process air, which had been dehumidified in advance. Systems installed with the two evaporative coolers were compared to determine which one was more energy efficient and which one could provide better thermal comfort for building occupants in a given climate zone, using detailed simulation data. The detailed energy consumption data of these two systems were estimated using an engineering equation solver with each component model. The results showed that the liquid desiccant and dew-point evaporative-cooler-assisted 100% outdoor air system (LDEOAS) resulted in approximately 34% more annual primary energy consumption than that of the liquid desiccant and the indirect and direct evaporative-cooler-assisted 100% outdoor air system (LDIDECOAS). However, the LDEOAS could provide drier and cooler supply air, compared with the LDIDECOAS. In conclusion, LDIDECOAS has a higher energy saving potential than LDEOAS, with an acceptable level of thermal comfort.en_US
dc.description.sponsorshipThis research was funded by the National Research Foundation of Korea (NRF) grant (No. 2019R1A2C2002514) and the Korean Institute of Energy Technology Evaluation and Planning (KETEP) (No. 20184010201710).en_US
dc.language.isoenen_US
dc.publisherMDPIen_US
dc.subjectliquid desiccant systemen_US
dc.subjectenergy simulationen_US
dc.subjectdew point indirect evaporative cooleren_US
dc.subjectevaporative cooleren_US
dc.titleEnergy Performance Comparison between Two Liquid Desiccant and Evaporative Cooling-Assisted Air Conditioning Systemsen_US
dc.typeArticleen_US
dc.relation.volume13-
dc.identifier.doi10.3390/en13030522-
dc.relation.page1-21-
dc.relation.journalENERGIES-
dc.contributor.googleauthorLiu, Su-
dc.contributor.googleauthorJeong, Jae-Weon-
dc.relation.code2020046113-
dc.sector.campusS-
dc.sector.daehakCOLLEGE OF ENGINEERING[S]-
dc.sector.departmentDEPARTMENT OF ARCHITECTURAL ENGINEERING-
dc.identifier.pidjjwarc-
dc.identifier.researcherIDK-6463-2017-
dc.identifier.orcidhttp://orcid.org/0000-0002-5391-3298-


qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

BROWSE