dc.description.abstractThe purpose of this paper is to evaluate energy and operating performance of a vacuum membrane dehumidification (VMD) system-assisted variable air volume (VAV) air conditioning system. The proposed system mainly consists of a vacuum membrane dehumidifier for controlling latent cooling load, and a cooling coil for controlling sensible cooling load. The VMD system dehumidifies the humid process air owing to the pressure difference between the membrane layer. Therefore, the VMD can independently provide latent cooling without the temperature change. The air passing through the VMD is then sensibly cooled by the cooling coil to meet the target supply air condition. To evaluate the energy saving potential of a proposed system, the energy and operating performance in cooling seasons were compared with that of a conventional VAV system via a series of energy simulation using the TRNSYS 18 program and engineering equation solver (EES). The results showed that the latent cooling load from a proposed system was 45% less than that of a reference system, and saved 16% of the primary energy consumption compared with the reference system.en_US
dc.language.isoko_KRen_US
dc.publisher(사)한국건축친환경설비학회en_US
dc.subject기체분리막 기반 제습시스템en_US
dc.subject변풍량 공조시스템en_US
dc.subject에너지 시뮬레이션en_US
dc.subjectVacuum membrane dehumidification systemen_US
dc.subjectVAV systemen_US
dc.subjectEnergy simulationen_US
dc.title기체 분리막 제습 장치가 적용된 변풍량 공조 시스템의 에너지 성능 분석en_US
dc.title.alternativeEnergy benefits of a vacuum membrane dehumidification system-assisted variable air volume air-conditioning systemen_US
dc.typeArticleen_US
dc.relation.page232-233-
dc.contributor.googleauthor조혜진-
dc.contributor.googleauthor천성용-
dc.contributor.googleauthor임려화-
dc.contributor.googleauthor정재원-
dc.contributor.googleauthorCho, Hye-Jin-
dc.contributor.googleauthorCheon, Seong-Yong-
dc.contributor.googleauthorLin, Li-Hua-
dc.contributor.googleauthorJeong, Jae-Weon-
dc.sector.campusS-
dc.sector.daehakCOLLEGE OF ENGINEERING[S]-
dc.sector.departmentDEPARTMENT OF ARCHITECTURAL ENGINEERING-
dc.identifier.pidjjwarc-
Appears in Collections:
COLLEGE OF ENGINEERING[S](공과대학) > ARCHITECTURAL ENGINEERING(건축공학부) > Articles
Files in This Item:
There are no files associated with this item.
Export
RIS (EndNote)
XLS (Excel)
XML


qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

BROWSE