dc.description.abstract | A liquid desiccant-assisted dedicated outdoor air system (LDADOAS) with organic Rankine cycle (ORC) was proposed as a centralized ventilation system applicable to high-rise apartment buildings. The LDADOAS consists of a liquid desiccant dehumidifier and an indirect evaporative cooler for conditioning the minimum required outdoor air ventilation. The ORC considered in this research is a combined heat and power system to accommodate common electricity demand of the apartment building. The heat released from the ORC is used for regeneration of the desiccant solution in the proposed system. Energy performance of the proposed system was compared with existing dedicated outdoor air systems via detailed energy simulation. The result showed that the LDADOAS consumed 48% less primary energy consumption compared with conventional dedicated outdoor air system considered in this work because most of regeneration heat required for the proposed system was supplied by the waste heat recovered from the ORC. | en_US |
dc.description.sponsorship | 본 연구는 2019년도 국토교통과학기술진흥원의 재원으로 국토교통기술촉진연구사업의 지원을 받아 수행한 연구 과제입니다(No.19CTAP-C141826-02). | en_US |
dc.language.iso | ko_KR | en_US |
dc.publisher | 한국건축친환경설비학회 | en_US |
dc.subject | 유기랭킨사이클 | en_US |
dc.subject | 액체식 제습 시스템 | en_US |
dc.subject | 외기전담 시스템 | en_US |
dc.subject | 중앙 환기 | en_US |
dc.subject | 공동주택 | en_US |
dc.subject | Organic Rankine cycle | en_US |
dc.subject | Liquid desiccant system | en_US |
dc.subject | Central ventilation system | en_US |
dc.subject | Dedicated outdoor air system | en_US |
dc.subject | Apartment building | en_US |
dc.title | 유기랭킨사이클을 결합한 제습증발냉각 기반 공동주택 중앙 환기 시스템의 에너지 성능 분석 | en_US |
dc.title.alternative | Energy Performance Analysis of Liquid Desiccant Assisted-Dedicated Outdoor Air System with Organic Rankine Cycle to an Apartment Central Ventilation System | en_US |
dc.type | Article | en_US |
dc.relation.no | 5 | - |
dc.relation.volume | 13 | - |
dc.identifier.doi | 10.22696/jkiaebs.20190034 | - |
dc.relation.page | 394-402 | - |
dc.relation.journal | 한국건축친환경설비학회 논문집 | - |
dc.contributor.googleauthor | 김범준 | - |
dc.contributor.googleauthor | 동혜원 | - |
dc.contributor.googleauthor | 정재원 | - |
dc.contributor.googleauthor | Kim, Beom-Jun | - |
dc.contributor.googleauthor | Dong, Hye-Won | - |
dc.contributor.googleauthor | Jeong, Jae-Weon | - |
dc.relation.code | 2019035007 | - |
dc.sector.campus | S | - |
dc.sector.daehak | COLLEGE OF ENGINEERING[S] | - |
dc.sector.department | DEPARTMENT OF ARCHITECTURAL ENGINEERING | - |
dc.identifier.pid | jjwarc | - |
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.