Improved Direct Power Control for Grid-Connected Voltage Source Converters
- Title
- Improved Direct Power Control for Grid-Connected Voltage Source Converters
- Author
- 정정주
- Keywords
- DC-AC power converters; direct power control (DPC); exponentially stable; linear time-invariant (LTI) system
- Issue Date
- 2018-10
- Publisher
- IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
- Citation
- IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, v. 65, no. 10, page. 8041-8051
- Abstract
- A novel grid voltage modulated direct power control (GVM-DPC) strategy for a grid-connected voltage source converter is proposed to control the instantaneous active and reactive powers directly. The GVM-DPC method consists of a nonlinear GVM controller, a conventional controller (feedforward and PI feedback), and nonlinear damping. The proposed control strategy shows a relationship between DPC and voltage-oriented control methods designed in d-q frame. The main advantage is that the proposed method makes the system be a linear time-invariant system, which enables us to apply various control methods easily. The GVM-DPC guarantees not only the convergence rate but also the steady-state performance of the system. Moreover, it is ensured that the closed-loop system is exponentially stable. Finally, simulation and experimental results using a 2.2-kVA VSC are provided to validate the tracking performance and robustness of the proposed control architecture. In addition, the total harmonic distortion of the current is 1.9% which is much less than the requirement for grid operation.
- URI
- https://ieeexplore.ieee.org/document/8291834https://repository.hanyang.ac.kr/handle/20.500.11754/120372
- ISSN
- 0278-0046; 1557-9948
- DOI
- 10.1109/TIE.2018.2801835
- Appears in Collections:
- COLLEGE OF ENGINEERING[S](공과대학) > ELECTRICAL AND BIOMEDICAL ENGINEERING(전기·생체공학부) > Articles
- Files in This Item:
There are no files associated with this item.
- Export
- RIS (EndNote)
- XLS (Excel)
- XML