202 0

Full metadata record

DC FieldValueLanguage
dc.contributor.author정재원-
dc.date.accessioned2019-12-03T05:36:07Z-
dc.date.available2019-12-03T05:36:07Z-
dc.date.issued2017-12-
dc.identifier.citationBUILDING AND ENVIRONMENT, v. 126, page. 348-354en_US
dc.identifier.issn0360-1323-
dc.identifier.issn1873-684X-
dc.identifier.urihttps://www.sciencedirect.com/science/article/pii/S0360132317304730?via%3Dihub-
dc.identifier.urihttps://repository.hanyang.ac.kr/handle/20.500.11754/116848-
dc.description.abstractThe objective of this study was to measure the mass and number loading of particles in supply ducts of homes with different mechanical fan operation conditions. Fifteen occupied single-family homes were selected from three multi-family residential complexes located in suburban areas of Seoul. The sample homes have mechanical ventilation systems that operate independently of heating and cooling devices. Field measurements consisted of three parts: a questionnaire regarding the indoor environment and occupant behavior related to ventilation; measurements of size resolved particle concentrations before and after operating the mechanical fan; an inspection of the proper installation of a filter unit and airflow in the supply ducts. The PM10 mass loading in the supply ducts ranged from 13.0 to 450 mg/m(2). The mass and number loading of particles in the supply ducts increased exponentially according to the built year of homes. The averaged PM10 loadings for two, five, and seven years after built were 11.6, 39.0, and 114.8 mg/m(2), respectively. Most of the occupants, 10 of 15 (67%), did not use mechanical fans to ventilate their homes, and the operation time of the mechanical fan significantly influenced on the particle loading rate in the supply ducts.en_US
dc.description.sponsorshipThis work was supported by National Research Foundation of Korea (NRF) with a grant funded by the Korean government (MEST) (NRF-2017R1A2B3009344). The authors thank B. D. Seo and M. Y. Cui who were graduate students for helping with the field measurements.en_US
dc.language.isoen_USen_US
dc.publisherPERGAMON-ELSEVIER SCIENCE LTDen_US
dc.subjectParticle loading rateen_US
dc.subjectParticle resuspensionen_US
dc.subjectSupply ductsen_US
dc.subjectMechanical ventilationen_US
dc.subjectOccupant behavioren_US
dc.subjectHomeHomeen_US
dc.titleMass loading of particles in the supply ducts of mechanical ventilation systems in homesen_US
dc.typeArticleen_US
dc.relation.no1-
dc.relation.volume126-
dc.identifier.doi10.1016/j.buildenv.2017.10.015-
dc.relation.page348-354-
dc.relation.journalBUILDING AND ENVIRONMENT-
dc.contributor.googleauthorPark, J. S.-
dc.contributor.googleauthorJeong, Jae-Weon-
dc.relation.code2017011893-
dc.sector.campusS-
dc.sector.daehakCOLLEGE OF ENGINEERING[S]-
dc.sector.departmentDEPARTMENT OF ARCHITECTURAL ENGINEERING-
dc.identifier.pidjjwarc-
Appears in Collections:
COLLEGE OF ENGINEERING[S](공과대학) > ARCHITECTURAL ENGINEERING(건축공학부) > Articles
Files in This Item:
There are no files associated with this item.
Export
RIS (EndNote)
XLS (Excel)
XML


qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

BROWSE