Impact of district heat source on primary energy savings of a desiccant-enhanced evaporative cooling system
- Title
- Impact of district heat source on primary energy savings of a desiccant-enhanced evaporative cooling system
- Author
- 정재원
- Keywords
- District heating; Energy simulation; Regenerator; Liquid desiccant; Evaporative cooling
- Issue Date
- 2017-03
- Publisher
- PERGAMON-ELSEVIER SCIENCE LTD
- Citation
- ENERGY, v. 123, page. 432-444
- Abstract
- The purpose of this research is to evaluate the primary energy savings of a desiccant-enhanced evaporative (DEVap) cooling system with a district heat source. The DEVap system consists of an internally cooled liquid desiccant dehumidifier and dew point evaporative cooler connected in series. The liquid desiccant unit requires a heat source for regenerating the weak desiccant solution, which means that the DEVap cooler is a thermally driven cooling system. It can provide energy benefits when the supplied heat comes from waste heat or renewable heat sources. In this research, district heat obtained from a combined heat and power (CHP) system was used as the heat source for the DEVap system. The primary energy consumption and CO2 emission rate of the proposed system with a district heat source were estimated using a detailed energy simulation and compared with those powered by a conventional gas boiler. The results showed that the DEVap system with district heat source consumed 46.2% less primary energy and produced 40.5% less CO2 compared with the system using the conventional gas boiler. (C) 2017 Elsevier Ltd. All rights reserved.
- URI
- https://www.sciencedirect.com/science/article/abs/pii/S0360544217301792?via%3Dihubhttps://repository.hanyang.ac.kr/handle/20.500.11754/113212
- ISSN
- 0360-5442; 1873-6785
- DOI
- 10.1016/j.energy.2017.02.005