Full metadata record
DC Field | Value | Language |
---|---|---|
dc.contributor.author | 정재원 | - |
dc.date.accessioned | 2019-11-20T07:56:42Z | - |
dc.date.available | 2019-11-20T07:56:42Z | - |
dc.date.issued | 2017-02 | - |
dc.identifier.citation | 한국건축친환경설비학회 논문집, v. 11, no. 1, page. 21-26 | en_US |
dc.identifier.issn | 1976-6483 | - |
dc.identifier.uri | http://www.dbpia.co.kr/journal/articleDetail?nodeId=NODE07135808&language=ko_KR | - |
dc.identifier.uri | https://repository.hanyang.ac.kr/handle/20.500.11754/112634 | - |
dc.description.abstract | The purpose of this paper is to evaluate the applicability of a liquid desiccant and evaporative cooling assisted 100% out door air system (LD-IDECOAS) in underground spaces. Detailed energy simulation is performed for estimating the energy saving potential of the LD-IDECOAS. Simulation is conducted using TRNSYS 17 and a commercial engineering equation solver program (EES). The district heating system in the LD-IDECOAS supplies heat energy for regeneration of desiccant. Thermal load of the underground spaces shows different pattern compared with that of the above ground space. Thermal load of underground space showed smaller variation compared with that of above ground space because of less changes of surroundings. As a results, LD-IDECOAS of underground spaces is show energy saving potential compared to the LD-IDECOAS of above ground space. | en_US |
dc.description.sponsorship | 이 논문은 2016년도 미래창조과학부의 재원으로 한국 연구재단의 지원을 받아 수행된 연구임 (No.2015R1A2 A1A005001726). 한, 2016년도 국토교통과학기술진흥 원의 국토교통기술진연구사업 지원에 의해 수행되었 음(16CTAP-C116268-01) | en_US |
dc.language.iso | ko_KR | en_US |
dc.publisher | 한국건축친환경설비학회 | en_US |
dc.subject | 제습증발냉각기반 전외기 공조시스템 | en_US |
dc.subject | 지중공간 | en_US |
dc.subject | 지역난방 | en_US |
dc.subject | LD-IDECOAS | en_US |
dc.subject | Underground spaces | en_US |
dc.subject | District heating | en_US |
dc.title | 제습증발냉각기반 전외기 공조시스템의 지상 및 지중 공간 적용에 따른 에너지 소비분석 | en_US |
dc.title.alternative | Energy Consumption of Liquid Desiccant and Evaporative Cooling-assisted 100% Outdoor Air System (LD-IDECOAS) in Underground and Above ground spaces | en_US |
dc.type | Article | en_US |
dc.relation.no | 1 | - |
dc.relation.volume | 11 | - |
dc.relation.page | 21-26 | - |
dc.relation.journal | 한국건축친환경설비학회 논문집 | - |
dc.contributor.googleauthor | 최은지 | - |
dc.contributor.googleauthor | 최병남 | - |
dc.contributor.googleauthor | 정재원 | - |
dc.contributor.googleauthor | Choi, Eun-Ji | - |
dc.contributor.googleauthor | Choi, Byoung-Nam | - |
dc.contributor.googleauthor | Jeong, Jae-Weon | - |
dc.relation.code | 2017018978 | - |
dc.sector.campus | S | - |
dc.sector.daehak | COLLEGE OF ENGINEERING[S] | - |
dc.sector.department | DEPARTMENT OF ARCHITECTURAL ENGINEERING | - |
dc.identifier.pid | jjwarc | - |
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.