The main purpose of this research is to analyze and compare the energy performance of two different air systems in various climatic zones (cold, mild, hot summer and cold winter, and hot summer and warm winter): the one is the dedicated outdoor air system (DOAS) with a parallel system and the other is the heat pump-integrated liquid desiccant and evaporative cooling-assisted 100% outdoor air system (HPLD-IDECOAS). The results showed that the HPLD-IDECOAS has higher energy saving potential up to 37% than the DOAS with parallel system in all climatic zones.