변풍량 공조시스템의 환기량 제어 및 이코노마이저 운전에 따른 학교건물의 환기 기준 별 에너지 소비량 분석

Title
변풍량 공조시스템의 환기량 제어 및 이코노마이저 운전에 따른 학교건물의 환기 기준 별 에너지 소비량 분석
Other Titles
Energy Consumption Analysis According to Ventilation Standard Variation of School Building in VAV System Operation Methods
Author
정재원
Keywords
수요기반환기시스템; 이코노마이저운전; 에너지 소비량; 환기기준; 학교 건물; Demand controlled ventilation; Economizer cycle; Energy consumption; Ventilation standard; School building
Issue Date
2019-05
Publisher
대한설비공학회
Citation
설비공학 논문집, v. 31, NO 5, Page. 227-235
Abstract
The objective of this study was to analyze the energy consumption of domestic and foreign ventilation standards as applied to the operation methods of variable air volume system in existing school building. The methods of operation for variable air volume system include; demand-controlled ventilation system (DCV) and the economizer system. It was revealed that domestic standard used more cooling energy compared to ASHRAE standard in DCV. This is because domestic standard introduces more return air which is warmer than outdoor air enthalpy in semester. It was also revealed that the cooling energy consumption in economizer similar in both standards. This is because when the outdoor air condition at the set point of supply and room air are constant in the two standards, the outdoor air introduction rate is similar. Therefore, the domestic ventilation standard is expected to have an improved energy consumption and indoor air quality.
URI
http://www.dbpia.co.kr/journal/articleDetail?nodeId=NODE08008059&language=ko_KRhttps://repository.hanyang.ac.kr/handle/20.500.11754/111401
ISSN
1229-6422; 2465-7611
DOI
10.6110/KJACR.2019.31.5.227
Appears in Collections:
COLLEGE OF ENGINEERING[S](공과대학) > ARCHITECTURAL ENGINEERING(건축공학부) > Articles
Files in This Item:
There are no files associated with this item.
Export
RIS (EndNote)
XLS (Excel)
XML


qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

BROWSE