간접식 증발냉각 시스템의 공기유동 방법에 따른 성능 분석
- Title
- 간접식 증발냉각 시스템의 공기유동 방법에 따른 성능 분석
- Other Titles
- Experimental comparison of the performance of typical and regenerative indirect evaporative coolers
- Author
- 정재원
- Keywords
- 간접식 증발냉각 시스템; 재생형 증발냉각; 열교환기; Indirect evaporative cooler; Regenerative evaporative cooler; Heat exchanger
- Issue Date
- 2016-11
- Publisher
- 한국건축친환경설비학회
- Citation
- 한국건축친환경설비학회 2016년도 추계학술발표대회, Page. 49-50
- Abstract
- The main purpose of this research is to compare the performances of two selected operation modes in an indirect evaporative cooler: typical cross-flow operation and regenerative operation using outdoor air as redirected air. To compare the performance of each operation mode, experiments were conducted with changing outdoor air condition and airflow rate. Pressure drop and leaving air temperature were measured to evaluate the performances quantitatively. As the experimental results, better performance indices were shown with the typical cross-flow operation than regenerative operation showing higher wet bulb effectiveness, lower pressure drop, and lower leaving air temperature.
- URI
- http://www.auric.or.kr/User/Rdoc/DocRdoc.aspx?BrsDataBaseName=RDOC&PrimaryKey=344600&DBNM=RDCR#.XI70mCgzaUkhttps://repository.hanyang.ac.kr/handle/20.500.11754/101076
- Appears in Collections:
- COLLEGE OF ENGINEERING[S](공과대학) > ARCHITECTURAL ENGINEERING(건축공학부) > Articles
- Files in This Item:
There are no files associated with this item.
- Export
- RIS (EndNote)
- XLS (Excel)
- XML