330 0

An Active Feedforward Compensation for a Current Harmonics Reduction in Threephase Grid-connected Inverters

Title
An Active Feedforward Compensation for a Current Harmonics Reduction in Threephase Grid-connected Inverters
Author
김래영
Keywords
Active feed forward; harmonic compensation; low frequency transformer; low order harmonic; THD; weak grid
Issue Date
2013-11
Publisher
IEEE
Citation
IECON 2013 - 39th Annual Conference of the IEEE Industrial Electronics Society Industrial Electronics Society, IECON 2013 - 39th Annual Conference of the IEEE. :400-405 Nov, 2013
Abstract
The paper discusses the influence of a grid impedance, especially for a leakage inductance of a grid side transformer. The grid impedance does not usually take into account during the design stage of the current controller. As a result, low order harmonics in the grid current are distorted. In this paper, the active feed-forward compensation method is proposed for the purpose of attenuating the current distortion. The proposed method can be applied to L filter as well as LCL filter. The effectiveness of the method is verified through various simulations and experiments based on a 1.5kW voltage source inverter prototype
URI
http://ieeexplore.ieee.org/document/6699169/metricshttps://repository.hanyang.ac.kr/handle/20.500.11754/73257
ISBN
978-1-4799-0224-8
ISSN
1553-572X
DOI
10.1109/IECON.2013.6699169
Appears in Collections:
COLLEGE OF ENGINEERING[S](공과대학) > ELECTRICAL AND BIOMEDICAL ENGINEERING(전기·생체공학부) > Articles
Files in This Item:
There are no files associated with this item.
Export
RIS (EndNote)
XLS (Excel)
XML


qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

BROWSE