Energy saving potential of liquid desiccant in evaporative-cooling-assisted 100% outdoor air system

Title
Energy saving potential of liquid desiccant in evaporative-cooling-assisted 100% outdoor air system
Author
박준석
Keywords
Liquid desiccant system; Evaporative cooling system; 100% Outdoor air system; Energy simulation
Issue Date
2013-09
Publisher
Elsevier Science B.V., Amsterdam.
Citation
Energy, 2013, 59, p.726-736
Abstract
The primary goal of this paper is to suggest integration of a liquid desiccant system into an evaporative-cooling-assisted 100% outdoor air system. Detailed energy simulation is performed for estimating the impact of the liquid desiccant system in indirect and direct evaporative cooler operations. The energy saving potential of the proposed system versus a conventional VAV (variable air volume) system is predicted via a series of energy simulations using TRNSYS 16 and a commercial equation solver program. Impact of water-side free cooling and solar thermal system on the operating energy saving of the liquid desiccant system is quantitatively evaluated. Simulation results showed that the proposed system consumes 51% less cooling energy compared to the conventional VAV system; primarily due to the water-side free cooling in maintaining the absorber temperature of the liquid desiccant system. The solar water heating system for regenerating the desiccant solution also contributes to the reduction in operating energy.
URI
https://www.sciencedirect.com/science/article/pii/S0360544213006051?via%3Dihubhttp://hdl.handle.net/20.500.11754/50308
ISSN
0360-5442
DOI
10.1016/j.energy.2013.07.018
Appears in Collections:
COLLEGE OF ENGINEERING[S](공과대학) > ARCHITECTURAL ENGINEERING(건축공학부) > Articles
Files in This Item:
There are no files associated with this item.
Export
RIS (EndNote)
XLS (Excel)
XML


qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

BROWSE