dc.description.abstract | The main purpose of this research was to propose a packed tower dehumidification effectiveness correlation useful for liquid desiccant integrated system design and analysis. In this research, liquid desiccant system’s performance data collected from established literatures were statistically analyzed using the 2<SUP>k</SUP>-factorial design method. The conventional desiccant solutions; LiCl and LiBr solutions used in a packed tower type absorber were analyzed. The proposed model predicts the dehumidification effectiveness of a packed tower type liquid desiccant dehumidification unit as a function of four quantitative system operation parameters. The impact of each system operation parameters on the dehumidification effectiveness were quantitatively estimated. It was found that the proposed model can be used to predict the dehumidification effectiveness, using LiCl solution within 9%, using LiBr solution within 4%, respectively. | en_US |
dc.description.sponsorship | 이 논문은 2013년도 정부의 재원으로 한국연구재단의 지원을 받아 수행된 연구임 (NRF-2012R1A2A1A01001927). 또한, 본 연구는 미래창조과학부 및 정보통신산업진흥원의 IT융합 고급인력과정 지원사업의 연구결과로 수행되었음(NIPA-2013-H0401-13-1003). | en_US |
dc.language.iso | ko_KR | en_US |
dc.publisher | 대한건축학회(The Architectural Institute of Korea) | en_US |
dc.subject | 액체식 제습 시스템 | en_US |
dc.subject | 충진탑식 제습기 | en_US |
dc.subject | 제습효율 예측모델 | en_US |
dc.subject | 염화리튬 | en_US |
dc.subject | 브롬화 리튬 | en_US |
dc.subject | Liquid desiccant system | en_US |
dc.subject | Packed tower system | en_US |
dc.subject | Dehumidification effectiveness model | en_US |
dc.subject | LiCl | en_US |
dc.subject | LiBr | en_US |
dc.title | 충진탑(Packed Tower)이 적용된 액체식 제습시스템의 제습효율 예측모델에 관한 연구 | en_US |
dc.title.alternative | Development of a Dehumidification Effectiveness Prediction Model for a Liquid Desiccant System with a Packed Tower | en_US |
dc.type | Article | en_US |
dc.relation.no | 10 | - |
dc.relation.volume | 29 | - |
dc.relation.page | 259-266 | - |
dc.relation.journal | 대한건축학회논문집 계획계 | - |
dc.contributor.googleauthor | 박준영 | - |
dc.contributor.googleauthor | 조홍재 | - |
dc.contributor.googleauthor | 김민휘 | - |
dc.contributor.googleauthor | 정재원 | - |
dc.contributor.googleauthor | Park, Joon-Young | - |
dc.contributor.googleauthor | Cho, Hong-Jae | - |
dc.contributor.googleauthor | Kim, Min-Hwi | - |
dc.contributor.googleauthor | Jeong, Jae-Weon | - |
dc.relation.code | 2012233169 | - |
dc.sector.campus | S | - |
dc.sector.daehak | COLLEGE OF ENGINEERING[S] | - |
dc.sector.department | DEPARTMENT OF ARCHITECTURAL ENGINEERING | - |
dc.identifier.pid | jjwarc | - |
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.