충진탑(Packed Tower)이 적용된 액체식 제습시스템의 제습효율 예측모델에 관한 연구
- Title
- 충진탑(Packed Tower)이 적용된 액체식 제습시스템의 제습효율 예측모델에 관한 연구
- Other Titles
- Development of a Dehumidification Effectiveness Prediction Model for a Liquid Desiccant System with a Packed Tower
- Author
- 정재원
- Keywords
- 액체식 제습 시스템; 충진탑식 제습기; 제습효율 예측모델; 염화리튬; 브롬화 리튬; Liquid desiccant system; Packed tower system; Dehumidification effectiveness model; LiCl; LiBr
- Issue Date
- 2013-10
- Publisher
- 대한건축학회(The Architectural Institute of Korea)
- Citation
- 대한건축학회 논문집(계획계), 2013, 29(10), P.259-266
- Abstract
- The main purpose of this research was to propose a packed tower dehumidification effectiveness correlation useful for liquid desiccant integrated system design and analysis. In this research, liquid desiccant system’s performance data collected from established literatures were statistically analyzed using the 2<SUP>k</SUP>-factorial design method. The conventional desiccant solutions; LiCl and LiBr solutions used in a packed tower type absorber were analyzed. The proposed model predicts the dehumidification effectiveness of a packed tower type liquid desiccant dehumidification unit as a function of four quantitative system operation parameters. The impact of each system operation parameters on the dehumidification effectiveness were quantitatively estimated. It was found that the proposed model can be used to predict the dehumidification effectiveness, using LiCl solution within 9%, using LiBr solution within 4%, respectively.
- URI
- http://www.dbpia.co.kr/Article/NODE02267843http://hdl.handle.net/20.500.11754/44779
- ISSN
- 1226-9093
- Appears in Collections:
- COLLEGE OF ENGINEERING[S](공과대학) > ARCHITECTURAL ENGINEERING(건축공학부) > Articles
- Files in This Item:
There are no files associated with this item.
- Export
- RIS (EndNote)
- XLS (Excel)
- XML