128 0

액체식 제습시스템 수조 내 수용액 농도 유지를 위한 멤브레인 적용성 분석

Title
액체식 제습시스템 수조 내 수용액 농도 유지를 위한 멤브레인 적용성 분석
Other Titles
Applicability of Membrane for Maintaining the Solution Concentration in the Sump of a Liquid Desiccant System
Author
정재원
Keywords
액체식 제습 시스템; 멤브레인; 수용액 농도; 물질 전달 저항; Liquid desiccant system; Membrane; Solution concentration; Mass transfer resistance
Issue Date
2020-11
Publisher
(사)대한설비공학회
Citation
대한설비공학회 동계학술발표회 논문집, page. 128-131
Abstract
This study aimed to evaluate the applicability of a membrane for maintaining the solution concentration in the sump of a liquid desiccant system. The mass transfer rate and the variation of the solution concentration were compared according to the mass transfer resistance of a membrane to evaluate the applicability of a membrane. The mass transfer resistance of the case 1, 2, and 3 were assumed to be 100, 350, and is 600 s/m, respectively. The results showed that the smaller mass transfer resistance, the more mass transfer rate. The difference of the solution concentration in the absorber and regenerator sump was also compared. The difference of the solution concentration of the case 1 is less than the caes 2 and case 3. Therefore, the membrane with low mass transfer resistance is advantageous in terms of maintaining the concentration of the solution in a liquid desiccant system.
URI
https://www.auric.or.kr/User/Rdoc/DocRdoc.aspx?BrsDataBaseName=RDOC&PrimaryKey=402597&DBNM=RDCR#.YwbOfHZByUkhttps://repository.hanyang.ac.kr/handle/20.500.11754/172702
Appears in Collections:
COLLEGE OF ENGINEERING[S](공과대학) > ARCHITECTURAL ENGINEERING(건축공학부) > Articles