해석 및 측정을 통한 시스순환전류 특성 및 상승원인 검토
- Title
- 해석 및 측정을 통한 시스순환전류 특성 및 상승원인 검토
- Other Titles
- A Study on the Characteristic and Rising Cause of Sheath Circulating Current by Analysis and Measurement
- Author
- 양해원
- Keywords
- Underground transmission system; Sheath circulating current; Distribution cable; EMTP/ATPDraw
- Issue Date
- 2002-10
- Publisher
- 대한전기학회
- Citation
- 전기학회논문지 A권, v. 51A, no. 10, page. 525-533
- Abstract
- It is common to install multiple lines in the same route. Recently, excessive sheath
circulating current was partially measured in underground cable systems of KEPCO.
Especially, the installation type, unballance section length between joint boxes and
zero sequence current by distribution cable have an effect on the rising of sheath
circulating current in the underground transmission system. If excessive current flows
in sheath, sheath loss which is reduced the tansmission capacity is produced. This paper
describes the relation analysis of sheath circulating current and burying types. And
also, a detailed analysis on rising cause and characteristics of sheath circulating
current by considering various unballaned conditions presents using analysis and
measurement regarding cable systems which have the problem of excessive sheath
circulating current.
- URI
- http://www.dbpia.co.kr/journal/articleDetail?nodeId=NODE01245282?https://repository.hanyang.ac.kr/handle/20.500.11754/157731
- ISSN
- 1229-2443
- Appears in Collections:
- COLLEGE OF ENGINEERING SCIENCES[E](공학대학) > ELECTRICAL ENGINEERING(전자공학부) > Articles
- Files in This Item:
There are no files associated with this item.
- Export
- RIS (EndNote)
- XLS (Excel)
- XML