461 0

전향보상 전압의 위상 변화를 통한 단독운전 검출 방법의 계통 정상 상태의 성능 평가

Title
전향보상 전압의 위상 변화를 통한 단독운전 검출 방법의 계통 정상 상태의 성능 평가
Other Titles
Performance Evaluation of Islanding Detection Method by Phase Shifted Feed-Forward Voltage in Steady-State Grid Condition
Author
김성민
Keywords
Anti-islanding detection; Feed-forward voltage; Grid connected inverter; Grid frequency variation; SMS(Slip Mode Frequency Shift)
Issue Date
2018-12
Publisher
전력전자학회
Citation
전력전자학회 논문지, v. 23, No. 6, Page. 373-380
Abstract
This study proposes a new islanding detection method that uses the phase shift of feed–forward voltage and evaluates the performance of an existing method and the proposed method when the grid frequency changes within the allowable range under steady-state conditions. The investigated existing method, which is slip mode frequency shift (SMS), uses current phase shift to detect islanding. The SMS method supplies reactive current to the grid under this condition, but the proposed method does not generate additional reactive power because it does not depend on the current control loop. The performance in steady-state grid condition is evaluated through simulations and experiments.
URI
http://www.dbpia.co.kr/Article/NODE07578268https://repository.hanyang.ac.kr/handle/20.500.11754/99156