IEICE-INST ELECTRONICS INFORMATION COMMUNICATIONS ENG
Citation
IEICE ELECTRONICS EXPRESS, v. 14, No. 5, Page. 20170050
Abstract
Numerous loads require the installation of load transformers for electrical isolation or voltage matching. When these loads are powered by a single-phase on-line UPS system, a high magnitude of transient inrush current is often observed due to the energizing of the load transformer. In this paper, we propose a novel single-phase on-line UPS system that eliminates the generation of inrush current while powering multiple load transformers. The performance of the proposed single-phase UPS system is endorsed by our experimental results obtained using a small laboratory-sized prototype.