In order to reduce data center cooling energy, ASHRAE Technical Committee 9.9 expanded thermal environmental ranges for data centers and recommended using the economizer, and it has reduced data center cooling energy successfully. The main purpose of this research is to establish an energy optimization process for the air-side economizer in a modular data center with respect to various parameters (supply air conditions, server thermal characteristics, cooling system configurations, and heat exchange effectiveness), and to determine optimum supply air ranges through simulation. The cooling energy simulation is conducted for three types of air-side economizers by changing the supply air temperature (SAT) and heat exchanger effectiveness at 16 locations in South Korea based on the three thermal environmental ranges. The simulation result shows that the lowest cooling energy consumption appears when the computer room air handler (CRAH) SAT is within 18-23 degrees C, and at higher SAT conditions, the cooling energy consumption increases, since chiller energy reduction is offset by the increase in CRAH fan energy. (C) 2014 Elsevier Ltd. All rights reserved.
National Research Foundation of Korea (NRF) - Korean governmen Korea Evaluation Institute of Industrial Technology - Korean Government
en
PERGAMON-ELSEVIER SCIENCE LTD
Modular data center
Air-side economizer
Optimum supply air temperature ranges
Energy simulation
Optimum supply air temperature ranges of various air-side economizers in a modular data center
Article
77
10.1016/j.applthermaleng.2014.12.021
163-179
APPLIED THERMAL ENGINEERING
Park, Jun-Seok
Ham, Sang-Woo
Jeong, Jae-Weon
2015005714
S
COLLEGE OF ENGINEERING[S]
ARCHITECTURAL ENGINEERING
junpark